CPL - Chalmers Publication Library
| Utbildning | Forskning | Styrkeområden | Om Chalmers | In English In English Ej inloggad.

Voltage sag index calculation: Comparison between time-domain simulation and short-circuit calculation

J. M. Carvalho ; Roberto Chouhy Leborgne (Institutionen för energi och miljö, Elteknik) ; P. M. da Silveira ; M. H. J. Bollen
Electric Power Systems Research (0378-7796). Vol. 78 (2008), 4, p. 676-682.
[Artikel, refereegranskad vetenskaplig]

This paper describes a case study where voltage sags indices are estimated using Monte Carlo approach combined with ATP (Alternative Transient Program) and short-circuit calculation program. Voltage sag magnitude and frequency are used to evaluate the correlation between both programs. The results indicate that time-domain simulation and short-circuit calculation gives similar voltage sag indices. Considering the high correlation between the results, short-circuit calculation programs are preferable over the time-domain simulation tools as the modelling for time-domain simulation is more complex, time consuming, and rarely covers the whole network. (C) 2007 Elsevier B.V. All rights reserved.

Nyckelord: simulation, power quality, voltage sag (dip), STOCHASTIC PREDICTION