Frequency evaluation of the Nordic power system using PMU measurements

Mattias Persson (Institutionen för elektroteknik, Elkraftteknik) ; Peiyuan Chen (Institutionen för elektroteknik, Elkraftteknik)
IET Generation, Transmission and Distribution (17518687). Vol. 11 (2017), 11, p. 2879-2887.
[Artikel, refereegranskad vetenskaplig]

This study investigates the frequency behaviour in the Nordic power system (NPS) utilising phasor measurement units (PMUs) from different locations in the system. Different metrics are selected or proposed to quantify the system frequency response in case of major disturbances and of daily normal operations. Based on the collected PMU data, there are on average 17.5 major, generator disconnection related, disturbances per year. The maximum absolute rate of change of frequency exceeds 0.1 Hz/s for 20% of these disturbances. The average frequency nadir falls to 49.7 \Hz, and the average time to nadir is about 8.7 s. If wind turbines were to be requested to provide inertia support to the system, these four metrics indicate how often, how fast, for how much and for how long the wind turbines should act. Moreover, during daily normal operations, the system has in general longer duration of over-frequency (f > 50.1 Hz) than under-frequency (f < 49.9 Hz). These frequency deviations are observed to occur around the hourly clearing of the Nord Pool Spot market and, especially during the hours between 05:00 and 08:00. In order to improve the frequency quality, the Nordic system operators tested and implemented an automatic frequency restoration reserve (aFRR) in addition to the existing manual one. Based on a frequency evaluation, this aFRR is needed most during 4:45-08:15 and 22:00-23:30 o'clock in 2012 in the NPS.

Nyckelord: phasor measurement; power markets; wind turbines; frequency response; frequency evaluation; Nordic power system; NPS; PMU measurements; phasor measurement units; frequency behaviour; system frequency response; wind turbines; frequency deviations; Nord Pool Spot market; frequency quality; Nordic system operators; automatic frequency restoration reserve; FRR-A



Den här publikationen ingår i följande styrkeområden:

Läs mer om Chalmers styrkeområden  

Denna post skapades 2017-10-04. Senast ändrad 2017-10-09.
CPL Pubid: 252323

 

Läs direkt!


Länk till annan sajt (kan kräva inloggning)


Institutioner (Chalmers)

Institutionen för elektroteknik, Elkraftteknik

Ämnesområden

Energi
Hållbar utveckling
Reglerteknik

Chalmers infrastruktur