Toxic fluoride gas emissions from lithium-ion battery fires

Fredrik Larsson (Institutionen för fysik, Subatomär fysik och plasmafysik (Chalmers)) ; Petra Andersson ; Per Blomqvist ; Bengt-Erik Mellander (Institutionen för fysik, Subatomär fysik och plasmafysik (Chalmers))
Scientific Reports (2045-2322). Vol. 7 (2017), 10018, p. 1-13.
[Artikel, refereegranskad vetenskaplig]

Lithium-ion battery fires generate intense heat and considerable amounts of gas and smoke. Although the emission of toxic gases can be a larger threat than the heat, the knowledge of such emissions is limited. This paper presents quantitative measurements of heat release and fluoride gas emissions during battery fires for seven different types of commercial lithium-ion batteries. The results have been validated using two independent measurement techniques and show that large amounts of hydrogen fluoride (HF) may be generated, ranging between 20 and 200 mg/Wh of nominal battery energy capacity. In addition, 15–22 mg/Wh of another potentially toxic gas, phosphoryl fluoride (POF3), was measured in some of the fire tests. Gas emissions when using water mist as extinguishing agent were also investigated. Fluoride gas emission can pose a serious toxic threat and the results are crucial findings for risk assessment and management, especially for large Li-ion battery packs.



Den här publikationen ingår i följande styrkeområden:

Läs mer om Chalmers styrkeområden  

Denna post skapades 2017-08-31. Senast ändrad 2017-09-20.
CPL Pubid: 251555

 

Läs direkt!

Lokal fulltext (fritt tillgänglig)

Länk till annan sajt (kan kräva inloggning)