Laboratory study of driving rain resistance of four façade systems with window fittings - Experimental results of leakage flows

Lars-Erik Olsson (Institutionen för bygg- och miljöteknik)
Central Europe Towards Sustainable Building 2016: Innovations for Sustainable Future, CESB 2016; Prague; Czech Republic; 22 June 2016 through 24 June 2016 p. 1233-1240. (2016)
[Konferensbidrag, refereegranskat]

Facades generally experience leaks and driving rain is considered to be a significant source of moisture, which should be taken into account when carrying out moisture calculations for exterior walls. Water can leak into the exterior walls and facades to a greater or lesser extent. However, we lack specific information with details on the amount of penetrating water. Four facade systems have been examined. Three of the facade systems were different in that there was one ventilated system, one single-stage sealing system and two drained systems. To better understand the exact importance of seals and variations in installation and workmanship, these factors have also been studied. The measurements show significant water leakage where seals are absent. Even in cases with seals present, there are leakages. Although the installations were performed by professionals, it was still leaky which shows that facade systems with window fittings should be designed and tested for any anticipated defects in order to ensure that the exterior wall are not subject to moisture damage.

Nyckelord: Driving rain resistance; EN 12865; Fagade; Water leakage; Windows



Denna post skapades 2016-12-19. Senast ändrad 2017-04-13.
CPL Pubid: 246228

 

Institutioner (Chalmers)

Institutionen för bygg- och miljöteknik

Ämnesområden

Husbyggnad

Chalmers infrastruktur