CPL - Chalmers Publication Library
| Utbildning | Forskning | Styrkeområden | Om Chalmers | In English In English Ej inloggad.

Improvement of admittance measurements for modeling of an ungrounded reactor/transformer winding

Tarik Abdulahovic (Institutionen för energi och miljö, Elteknik) ; Torbjörn Thiringer (Institutionen för energi och miljö, Elteknik)
International Journal of Modeling, Simulation, and Scientific Computing (1793-9623). Vol. 7 (2016), 3,
[Artikel, refereegranskad vetenskaplig]

In this paper, a model of an ungrounded reactor winding is developed for transient voltage studies. The developed model is a black box model where the state-space model is developed using the directly measured admittance matrix of the reactor winding. Furthermore, an improved model is developed, where the accuracy of the admittance matrix measurement set in the low frequency band is obtained indirectly using an additional set of voltage ratio measurements. When the measured admittances are low, the accuracy of the diagonal admittance vectors in the low frequency band is low as well. However, the accuracy at low frequencies obtained using the indirect measurements is improved at nodes with the lowest admittances. In this paper, different approaches for indirect measurements are studied and the most accurate method is identified considering the physical structure of windings.

Nyckelord: Transformer windings, impedance measurement, transient analysis



Denna post skapades 2016-11-02. Senast ändrad 2017-10-03.
CPL Pubid: 244659

 

Läs direkt!


Länk till annan sajt (kan kräva inloggning)


Institutioner (Chalmers)

Institutionen för energi och miljö, Elteknik (2005-2017)

Ämnesområden

Datorteknik

Chalmers infrastruktur