Monte-Carlo analysis of wind farm lightning-surge transients aided by LINET lightning-detection network data

P. Sarajcev ; Josip Vasilj (Institutionen för signaler och system, Reglerteknik) ; D. Jakus
Renewable Energy (9601481). Vol. 99 (2016), p. 501-513.
[Artikel, refereegranskad vetenskaplig]

This paper presents a statistical method of analysis of wind farm lightning-surge transients, which employs a sophisticate wind farm high-frequency-transients model developed within the EMTP software package. The method features a Monte–Carlo simulation applied to the numerical analysis of wind farm lightning transients—which produces a statistical depiction of overvoltages distribution within the wind farm electrical network—that could be used in a statistical and semi-statistical methods of wind farm equipment insulation coordination, or it could assist in wind farm lightning risk management and surge protection optimisation. Wind farm lightning incidence is computed with the aid of the LINET lightning-detection network data, while at the same time accounting for the actual wind turbine geometry, exposure, and terrain topography (orography). Wind turbine effective height, in exposed locations, is determined from the physical postulates governing the initiation of lightning. Subsequently obtained wind farm equipment overvoltages are statistically described by means of the kernel density estimation procedure. The application of the proposed method on the actual onshore wind farm is provided in the paper as well.

Nyckelord: EMTP; Kernel density estimation; Lightning; LINET; Monte–Carlo method; Transient analysis; Wind farm



Denna post skapades 2016-08-31.
CPL Pubid: 241021

 

Läs direkt!


Länk till annan sajt (kan kräva inloggning)


Institutioner (Chalmers)

Institutionen för signaler och system, Reglerteknik

Ämnesområden

Reglerteknik

Chalmers infrastruktur