Comparison of PI and PR current controllers applied on two-level VSC-HVDC transmission system

Alisa Manoloiu ; Heverton A Pereira ; Remus Teodorescu ; Massimo Bongiorno (Institutionen för energi och miljö, Elteknik) ; Mircea Eremia ; Selenio R Silva
IEEE PowerTech 2015 p. Article no. 7232648. (2015)
[Konferensbidrag, refereegranskat]

This paper analyzes differences between αβ and dq reference frames regarding the control of two-level VSC-HVDC current loop and dc-link voltage outer loop. In the first part, voltage feedforward effect is considered with PI and PR controllers. In the second part, the feedforward effect is removed and the PR gains are tuned to keep the dynamic performance. Also, the power feedforward is removed and the outer loop PI controller is tuned in order to maintain the system dynamic performance. The paper is completed with simulation results, which highlight the advantages of using PR controller.



Den här publikationen ingår i följande styrkeområden:

Läs mer om Chalmers styrkeområden  

Denna post skapades 2015-09-22. Senast ändrad 2016-10-07.
CPL Pubid: 222973

 

Läs direkt!


Länk till annan sajt (kan kräva inloggning)


Institutioner (Chalmers)

Institutionen för energi och miljö, Elteknik (2005-2017)

Ämnesområden

Energi
Elkraftteknik

Chalmers infrastruktur