Ozone treatment of extract air from a restaurant kitchen with heat

Lars Ekberg (Institutionen för energi och miljö, Installationsteknik) ; John Woollett
Proceedings CLIMA 2013 – 11th REHVA World Congress (2013)
[Konferensbidrag, refereegranskat]

Ozone generation equipment was installed to reduce the cost of cleaning the fat out of the extract ducting system in a fast-food restaurant. The reduced fat content would also help to protect the air handling unit, which comprised recovery of heat from the extract air. However, there is a health respect for ozone, which is a highly reactive irritant. Chemical reactions may also lead to the production of nitrogen dioxide, aldehydes and other volatile organic compounds. Concentrations of the compounds mentioned were measured both by passive and active sampling. Measurements were made outdoors and indoors as well as in the supply, extract and exhaust air streams. With ozone generation the ozone concentration in the extract and exhaust air was higher than 450 µg/m3. However, no increase of the ozone concentration in the supply or indoor air was observed. There were no observations of any formaldehyde generation. Neither were there any signs of nitrogen dioxide generation influencing the supply or indoor air, although the exhaust air concentration was higher than the extract air concentration. The measurement results point to incomplete chemical reactions still occurring in the exhaust air. This indicates that the length of ducting available and the air speed did not leave enough time to complete the chemical reactions to break down the different contaminants. However, in this situation with a coil heat exchanger this is of no significance, but if a rotary heat exchanger was to be used, the design must allow enough reaction time at maximum flow.

Nyckelord: ozone generation; extract air; chemical reactions; heat-recovery; air quality



Den här publikationen ingår i följande styrkeområden:

Läs mer om Chalmers styrkeområden  

Denna post skapades 2014-01-17. Senast ändrad 2014-01-17.
CPL Pubid: 192815

 

Institutioner (Chalmers)

Institutionen för energi och miljö, Installationsteknik (2005-2014)

Ämnesområden

Building Futures
Energi
Hållbar utveckling
Samhällsbyggnadsteknik