Study of proper placements of HEPA-filter units in order to prevent airborne contamination of autoclaves in aseptic production by using computional fluid dynamics

Catinka Ullman (Institutionen för energi och miljö, Installationsteknik) ; Bengt Ljungqvist (Institutionen för energi och miljö, Installationsteknik) ; Berit Reinmüller (Institutionen för energi och miljö, Installationsteknik) ; Jenny Sahlén
Renhetsteknik Vol. 2013 (2013), 3, p. 15-20.
[Artikel, övrig]

Autoclaves are common process equipment used in the pharmaceutical industry. This type of process equipment can cause temperature differences relative to ambient air. During unloading autoclaves used for aseptic production, entrainment of room air into the loading chamers may occur creating contamination risks. To minimize these risks, high-efficiency particulate air filter units with unidirectional flow (UDF) can be used to provide the chamber openings with clean air protection. This paper describes the use of computational fluid dynamics to simulate unloading of autoclaves used for aseptic production in meaning to improve the understanding of contamination risks of the autoclave chamber and present solutions of proper placement of HEPA-filters in order to protect the openings of autoclaves.

Nyckelord: HEPA-filter, autoclaves



Den här publikationen ingår i följande styrkeområden:

Läs mer om Chalmers styrkeområden  

Denna post skapades 2014-01-14. Senast ändrad 2014-01-20.
CPL Pubid: 192366

 

Institutioner (Chalmers)

Institutionen för energi och miljö, Installationsteknik (2005-2014)

Ämnesområden

Building Futures
Hållbar utveckling
Annan medicin och hälsovetenskap

Chalmers infrastruktur