Operation of static series compensator under distorted utility conditions

Hilmy Awad (Institutionen för energi och miljö, Elteknik) ; H. Nelsen ; F. Blaabjerg ; M. J. Newman
IEEE Transactions on Power Systems (08858950 ). Vol. 20 (2005), 1, p. 448-457.
[Artikel, refereegranskad vetenskaplig]

The static series compensator (SSC) has shown a significant capability to mitigate voltage dips, which are the most severe problem to sensitive loads. Also, it has been declared that the function of the SSC can be extended to work as a series active filter. This paper proposes a moving-average filter to detect the fundamental component of the measured voltages and currents (needed to control the SSC) while using a double vector control algorithm to improve the transient performance of the SSC. This is made in order to accurately control the fundamental voltage component at the load terminals in the case of distorted grid voltage. Furthermore, a selective harmonic compensation strategy is applied to filter out the grid harmonics. The operation of the SSC under distorted utility conditions and voltage dips is discussed. The validity of the proposed controller is verified by experiments, carried out on a 10-kV SSC laboratory setup. Experimental results have shown the ability of the SSC to mitigate voltage dips and harmonics. It is also shown that the proposed controller has improved the transient performance of the SSC even under distorted utility conditions.



Denna post skapades 2010-01-25.
CPL Pubid: 110820

 

Läs direkt!


Länk till annan sajt (kan kräva inloggning)


Institutioner (Chalmers)

Institutionen för energi och miljö, Elteknik

Ämnesområden

Elektroteknik och elektronik

Chalmers infrastruktur